Home  | Site plan  | Careers  | Contact us  | Français  |

Products

Your sales contact: quotation@grimard.ca        Toll free: 1 (866) GRIMARD 

Low Voltage Switchgear

MetalGear

LV Metal-Enclosed Switchgear

Electrical features:
Rated insulation voltage V 635
Test voltage at power frequency kV 1 min 2.2
Rated frequency Hz 50/60
Rated short-time withstand current kA 1 s. 22 - 42 - 65
Peak current kA 3 cy. ... 149.5
Main busbar rated current A   800...5000  
Rated current of the branch connections A 800...5000

Downloads: MetalGear Flyer (PDF 1.59 MB) 

MetalGear-WS

MetalGear-WS - Space-Efficient LV Metal-Enclosed Switchgear

Electrical features:
Rated insulation voltage V 635
Test voltage at power frequency kV 1 min 2.2
Rated frequency Hz 50/60
Rated short-time withstand current kA 1 s. 22 - 42 - 65
Peak current kA 3 cy. ... 149.5
Main busbar rated current A   800...3200  
Rated current of the branch connections A 800...3200

Downloads: MetalGear-WS Flyer (PDF 1.99 MB) 

 DC Traction Switchgear

Electrical features:
Rated voltage VDC 800
Test voltage at power frequency kV 1 min 5.5
Rated short-time withstand current kA 120
Main busbar rated current A   2000...6000  
Rated current of the branch connections A 2000...6000

 AC and DC Switchboards

Electrical features:
Rated insulation voltage V 635
Test voltage at power frequency kV 1 min 2.2
Rated frequency Hz 50/60
Rated short-time withstand current kA 1 s. 22 - 42 - 65
Peak current kA 3 cy. ... 149.5
Main busbar rated current A   400...1600  
Rated current of the branch connections A 400...1600
Medium Voltage Switchgear

SafeClad

5-15 kV Arc Resistant Metal-Clad Switchgear with Arc Arrestor Technology

Electrical features: Rated voltage
5 kV 15 kV
Test voltage at power frequency kV 1 min 19 36
Impulse withstand voltage kV 60 95
Rated frequency Hz 60 60
Rated short-time withstand current kA 1 s. 12.5 - 25 - 31.5 - 40
Peak current kA 10 cy. 33.75 - 67.5 - 85 - 108
Arc-resistant accessibility type IEEE C37.20.7 2BC
Internal arc withstand current kA 12.5 - 25 - 31.5 - 40
Internal arc withstand duration sec. 0.5 - 1.0
Main busbar rated current A 1200 - 2000 - 3000
Rated current of the branch connections A 1200 - 2000 - 3000

 

Downloads: SafeClad Flyer (PDF 1.51 MB)

                  Arc Arrestor Flyer (PDF 1.41 MB)

                 Video of Arc Arrestor Technology (You Tube)

SafeClad-WS

15-27 kV Space-Efficient Arc Resistant Metal-Clad Switchgear with Arc Arrestor Technology

Electrical features: Rated voltage
15 kV 27 kV
Test voltage at power frequency kV 1 min 36 60
Impulse withstand voltage kV 95 125
Frequency Hz 60 60
Rated short-time withstand current kA 2 s 25; 31.5 25
Peak current kA 10 cy. 65; 82 65
Arc Resistant accessibility Type IEC 62217-200 A FLR
Internal arc withstand current kA 25; 31.5 25
Internal Arc duration sec. 0.5
Main busbar rated current A 1200; 2000 1200
Rated current of the branch connections A 1200; 2000 1200

Downloads: SafeClad-WS Flyer (PDF 1.99 MB) 

                   Arc Arrestor Flyer (PDF 1.41 MB)

                  Video of Arc Arrestor Technology (You Tube)

15-27 kV Metal-Enclosed Load Interrupter Switchgear

Electrical features: Rated voltage
15 kV 27 kV
Rated insulation voltage kV 1 min 36 60
Impulse withstand voltage kV 95 125
Frequency Hz 60 60
Rated short-time withstand current kA 1 s 25; 31.5; 40 25
Main busbar rated current A 600...2000 600...2000
Rated current of the branch connections A 600; 1200 600; 1200

 Generator Terminal Enclosure

Electrical features: Rated voltage
5 kV 15 kV
Test voltage at power frequency kV 1 min 19 36
Impulse withstand voltage kV 60 95
Frequency Hz 60 60
Rated short-time withstand current kA 1 s. 12.5 - 25 - 31.5 - 40
Peak current kA 10 cy. 33.75 - 67.5 - 85 - 108
Rated current A 1200...5000
Busduct System

 LV & MV Metal-Enclosed Non-Segregated Phase Busduct

Electrical features:            Rated voltage
600 V 5 kV 15 kV
Test voltage at power frequency kV 1 min 2.2 19 36
Impulse withstand voltage kV - 60 95
Rated frequency Hz 50-60 50-60 50-60
Rated short-time withstand current kA 1 s. 22-42-45 25-31.5-40
Peak current kA 3 cy.: 50.6-96.6-149.5 10 cy.: 67.5-85-108
Rated current A 1200...4000 1200...3000

Download: Busduct Flyer (PDF 1.51 MB)

Electrical House (E-House)

Walk-in Switchgear and Protection & Control Building

Protection and Control Panel

Generator Autosychronization, Protection and control System

Top of page

Grimard's main strength resides in the expertise of its five divisions and the synergy between them.

News

Grand opening of the Mistissini bridge
Read the rest »

Construction Grimard is moving !
Read the rest »